A 1000 KVA, 3000 v, 50 Hz, three-phase delta-connected alternator has an effective armature resistance of 0.2 Ω. A field current of 40 A produces a short- circuit current of 200 A, and an open-circuit voltage of 1040 V (line-to-line). Calculate the full load percentage voltage regulation at a power factor of 0.8 lagging. How will the regulation be affected if the alternator delivers its full load output at a power factor of 0.8 leading?

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter31: Three-phase Alternators
Section: Chapter Questions
Problem 1RQ: What conditions must be met before two alternators can be paralleled together?
icon
Related questions
icon
Concept explainers
Question

 A 1000 KVA, 3000 v, 50 Hz, three-phase delta-connected alternator has an effective armature resistance of 0.2 Ω. A field current of 40 A produces a short- circuit current of 200 A, and an open-circuit voltage of 1040 V (line-to-line). Calculate the full load percentage voltage regulation at a power factor of 0.8 lagging. How will the regulation be affected if the alternator delivers its full load output at a power factor of 0.8 leading?

Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Synchronous Motor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning